Serial number | Item | Unit | Data | ||
1 | Rated voltage | kV | 12 | 40.5 | |
2 | Rated frequency | Hz | 50/60 | ||
3 | Rated current | A |
1250/2500/3150
|
1250/2500
|
|
4 |
Rated power freguency
withstand voltage(1min)
|
Phases and to earth
|
kv |
42
|
95 |
Isolating distances
|
48 | 118 | |||
Rated lightning impluse
withstand voltage
|
Phases and to earth
|
75(95*)
|
185
|
||
Isolating distances |
85(110*)
|
215
|
|||
Power frequency withstand voltage
(Control and auxiliary circuit)
|
2 | ||||
5 |
Rated short-time withstand current
|
31.5/40
|
31.5
|
||
6 |
Rated peak withstand current
|
kA |
80/100
|
80 | |
7 |
Duration of rated short-circuit current
|
s | 4 | 4 | |
8 |
Rated short-circuit breaking current
|
kA |
31.5/40
|
31.5 | |
9 |
Rated short-circuit making current
|
kA | 80/100 | 80 | |
10 |
Arcing duration
|
s | 1 | 1 | |
11 |
Rated operating sequence
|
0-0.3s-CO-3min-CO
|
|||
12 |
Insulating gas
|
SF6
|
|||
13 |
Annual leakage rate
|
%
|
≤ 0.01
|
||
14 |
Standard degree of
protection
|
Sealed gas box
|
IP67
|
||
Switchgear enclosure
|
IP4X | ||||
15 |
Rated inflation pressure
|
MPa
|
0.03 | ||
Minimum functional level pressure
|
0.01 | ||||
16 |
Rated supply voltage of auxiliary circuit
|
V |
DC 24, 48, 110, 220, AC220
|
||
17 | Mechanical life |
Circuit breaker
|
Operation | 12000 | 12000 |
Isolation switch | 3000 | 3000 | |||
Earthing switch | 3000 | 3000 | |||
18 |
Electrical endurance of circuit breaker
|
Operation |
30(E2)
|
||
19 |
Loss of service continuity
|
LSC2A
|