11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271

Product Details
Customization: Available
Certification: ISO9001, IEC62271
Shell Material: Steel Plate
Still deciding? Get samples of $ !
Request Sample
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2025

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Cooperated with Fortune 500
This supplier has Cooperated with Fortune 500 companies
Self-branded
The supplier has 71 Self-brands, check the Audit Report for more information
to see all verified strength labels (29)
  • 11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271
  • 11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271
  • 11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271
  • 11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271
  • 11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271
  • 11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271
Find Similar Products
  • Overview
  • Standards & Specifications
Overview

Basic Info.

Model NO.
ZCKQG-12
Voltage Level
Medium Voltage
Installation
Fixed
Structure
Floorstanding
Current
AC
Rated Voltage
12kv
Loss of Service Continuity
Lsc2
Height
2000mm
Width
420mm
Depth
850mm
Transport Package
Aluminum Foil + Wooden Pallet
Trademark
Customized
Origin
China

Product Description


11kV 12kv Dry Air Insulated Environment Friendly Ring Main Unit for IEC62271 Standard
 
Serial number Item Unit Data
1 Rated voltage kV 12
2 Rated frequency Hz 50
3 Rated current A
630
4
Rated
insulation
level
Rated power frequency withstand voltage(1min)
kv
Between phases and to earth: 42
Isolating distances: 48
Rated lightning impluse withstand voltage
Between phases and to earth:75
Isolating distances: 85
Power frequency withstand voltage
(Control and auxiliary circuit)
2
5
Rated short-circuit breaking current
kA
20;25
6
Short circuit breaking times
Operation
30
7
Rated short-circuit making current
kA 50;63
8
Rated breaking current of single capacitor bank
A
630
9
Rated breaking current of back-to-back capacitor bank
A 400
10
Rated cable charging breaking current
A 50
11
Rated operating sequence
 
0-0.3s-CO-3min-CO
12
Rated gas
pressure at
20ºC
Rated inflation pressure
MPa
0.035
Minimum functional level pressure
0.01
13
Degree of
protection
Sealed gas box
 
IP67
Switchgear enclosure
  IP4X
14
Gas leakage rate per annual
% ≤0.01
15
Rated supply voltage of auxiliary circuit
Operation
AC380, AC220
16
Rated supply voltage of control circuit
 
DC110, DC220, AC220
17
Loss of service continuity
 
LSC2
 
Standards & Specifications
 
• IEC 62271-1: 2021 High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear
• IEC 62271-100: 2021 High-voltage switchgear and controlgear - Part 100: Alternating-current circuit breakers
• IEC 62271-200: 2021 High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 52kV
• IEC 60529: 1989+AMD1: 1999+AMD2: 2013 CSV Consolidated version Degrees of protection provided by enclosures (IP Code)
11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC6227111kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271
11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271
11kv 12kv Sf6 Free Dry Air Insulated Ring Main Unit for IEC62271

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier