Serial number | Item | Unit | Data | ||
1 | Rated voltage | kV | 24 | ||
2 | Rated frequency | Hz | 50 | ||
3 |
Rated insula-
tion levels
|
Rated power frequency withstand voltage (1min) | kV |
Between phases and to earth: 65
Across isolating distances: 79
|
|
Rated lighting impluse withstand voltage |
Between phases and to earth: 125
Across isolating distance: 145
|
||||
4 |
Rated secondary withstand voltage
|
V |
2000
|
||
5 |
Rated current
|
A | 1250 | 3150 | |
6 |
Rated short circuit breaking current
|
kA | 31.5 | 31.5 | |
7 |
Rated short-time withstand current
|
kA | 31.5 | 31.5 | |
8 |
Rated short-circuit closing circuit
|
kA | 80 | 80 | |
9 |
Rated peak withstand current
|
kA/s | 80 | 31.5 | |
10 |
Rated duration of short circuit
|
s | 4 | ||
11 |
Mechanical life
|
Time | 20000 | 10000 | |
12 | Electrical life | E2 | |||
13 | Rated breaking current of single/back-to-back capacitor bank | A | 630/400 | 800/400 | |
14 |
Rated operating voltage
|
V |
DC110/220,AC110/220,DC48V
|
||
15 |
Phase-to-phase center distance
|
mm |
275±2
|
275±2
|
|
16 |
Contact erosion limit
|
mm | |||
17 |
Opening time
|
ms |
35-55
|
||
18 |
Closing time
|
ms |
20~40
|
||
19 |
Contact closing bounce time
|
ms |
≤ 2
|
||
20 |
Synchronicity of opening and closing
|
ms |
≤ 2
|
||
21 |
Motor energy charging time
|
s |
≤ 12
|
||
22 |
Rated operation sequence
|
O -0.3s- CO -180s- CO
|
|||
23 |
Weight
|
kg | 230 | 350 | |
24 |
Dimension
|
mm | 852*771*797 | 922*815*787 |