12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin

Product Details
Customization: Available
Certification: ISO9001, IEC62271
Shell Material: Steel Plate
Still deciding? Get samples of $ !
Request Sample
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2025

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Cooperated with Fortune 500
This supplier has Cooperated with Fortune 500 companies
Self-branded
The supplier has 71 Self-brands, check the Audit Report for more information
to see all verified strength labels (29)
  • 12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin
  • 12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin
  • 12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin
  • 12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin
  • 12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin
  • 12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin
Find Similar Products
  • Overview
  • Standards & Specifications
Overview

Basic Info.

Model NO.
ZCSF-12/ZCSF-40.5
Voltage Level
Medium Voltage
Installation
Fixed
Structure
Cabinet
Current
AC
Rated Voltage
12/40.5kv
Loss of Service Continuity
Lsc2
Height
2200/2400mm
Width
450/500mm
Depth
750/1000mm
Transport Package
Aluminum Foil + Wooden Pallet
Trademark
Customized
Origin
China

Product Description

12kV 40.5kV Sf6 Ring Main Unit Rmu Switchgear For Power Transmission
Serial number Item Unit Data
1 Rated voltage kV 12 40.5
2 Rated frequency Hz 50/60
3 Rated current A
630
630/1250
4
Rated power freguency
withstand voltage(1min)
Phases and to earth
kv
42
95
Isolating distances
48 118
Rated lightning impluse
withstand voltage
Phases and to earth
75
185
Isolating distances
85
215
Power frequency withstand voltage
(Control and auxiliary circuit)
2
5
Rated short-time withstand current
kA
20/25
31.5
6
Rated peak withstand current
kA
50/63
80
7
Duration of rated short-circuit current
s 4 4
8
Rated short-circuit breaking current
kA
20/25
31.5
9
Rated short-circuit making current
kA
50/63
80
10
Arcing duration
s 1 1
11
Rated operating sequence
 
0-0.3s-CO-3min-CO
12
Insulating gas
 
SF6
13
Annual leakage rate
%
≤ 0.01
14
Standard degree of
protection
Sealed gas box
 
IP67
Switchgear enclosure
IP4X
15
Rated inflation pressure
MPa
0.03
Minimum functional level pressure
0.01
16
Rated supply voltage of auxiliary circuit
V
DC 24, 48, 110, 220, AC220
17 Mechanical life
Circuit breaker
Operation 10000 11000
Isolation switch 5000 3000
Earthing switch 5000 3000
18
Electrical endurance of circuit breaker
Operation
30(E2)
19
Loss of service continuity
 
LSC2
 
Standards & Specifications

• IEC 62271-1: 2021 High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear
• IEC 62271-100: 2021 High-voltage switchgear and controlgear - Part 100: Alternating-current circuit breakers
• IEC 62271-200: 2021 High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and  controlgear for rated voltages above 1kV and up to and including 52kV
• IEC 60529: 1989+AMD1:1999+AMD2:2013 CSV Consolidated version Degrees of protection provided by enclosures (IP Code)
12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin12kv 40.5kv IEC62271 Ring Main Unit Rmu for Prefabricated Power Cabin

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier