40.5kv Sf6 Gas Insulated Ring Main Unit Switchgear with Current 630-1250A 31.5ka

Product Details
Customization: Available
Certification: ISO9001, IEC62271
Shell Material: Steel Plate
Still deciding? Get samples of $ !
Request Sample
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2025

Suppliers with verified business licenses

Audited Supplier Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Cooperated with Fortune 500
This supplier has Cooperated with Fortune 500 companies
Self-branded
The supplier has 71 Self-brands, check the Audit Report for more information
to see all verified strength labels (29)
  • 40.5kv Sf6 Gas Insulated Ring Main Unit Switchgear with Current 630-1250A 31.5ka
  • 40.5kv Sf6 Gas Insulated Ring Main Unit Switchgear with Current 630-1250A 31.5ka
  • 40.5kv Sf6 Gas Insulated Ring Main Unit Switchgear with Current 630-1250A 31.5ka
  • 40.5kv Sf6 Gas Insulated Ring Main Unit Switchgear with Current 630-1250A 31.5ka
  • 40.5kv Sf6 Gas Insulated Ring Main Unit Switchgear with Current 630-1250A 31.5ka
  • 40.5kv Sf6 Gas Insulated Ring Main Unit Switchgear with Current 630-1250A 31.5ka
Find Similar Products
  • Overview
  • Standards & Specifications
Overview

Basic Info.

Model NO.
ZCSF-40.5
Voltage Level
Medium Voltage
Installation
Fixed
Structure
Cabinet
Current
AC
Rated Voltage
40.5kv
Loss of Service Continuity
Lsc2
Height
2200/2400mm
Width
500mm
Depth
1000mm
Transport Package
Aluminum Foil + Wooden Pallet
Trademark
Customized
Origin
China

Product Description

Rmu 40.5kV Gas Insulated Ring Main Unit Switchgear
 
umber Item Unit Data
1 Rated voltage kV 40.5
2 Rated frequency Hz 50/60
3 Rated current A
630/1250
4
Rated
insulation
level
Rated power frequency withstand voltage(1min)
kv
Between phases and to earth: 95
Isolating distances:118
Rated lightning impluse withstand voltage
Between phases and to earth:185
Isolating distances: 215
Power frequency withstand voltage
(Control and auxiliary circuit)
2
5
Rated short-circuit breaking current
kA
31.5
6
Short circuit breaking times
Operation
30
7
Rated short-circuit making current
kA 80
8
Rated breaking current of single capacitor bank
A
630
9
Rated breaking current of back-to-back capacitor bank
A 400
10
Rated cable charging breaking current
A 50
11
Rated operating sequence
 
0-0.3s-CO-3min-CO
12
Rated gas
pressure at
20ºC
Rated inflation pressure
MPa
0.03
Minimum functional level pressure
0.01
13
Degree of
protection
Sealed gas box
 
IP67
Switchgear enclosure
  IP4X
14
Gas leakage rate per annual
% ≤0.01
15
Rated supply voltage of auxiliary circuit
V
AC380, AC220
16
Rated supply voltage of control circuit
V
DC110, DC220, AC220
17
Loss of service continuity
 
LSC2
 
Standards & Specifications

• IEC 62271-1: 2021 High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear
• IEC 62271-100: 2021 High-voltage switchgear and controlgear - Part 100: Alternating-current circuit breakers
• IEC 62271-200: 2021 High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and  controlgear for rated voltages above 1kV and up to and including 52kV
• IEC 60529: 1989+AMD1:1999+AMD2:2013 CSV Consolidated version Degrees of protection provided by enclosures (IP Code)